No ac found system off upon arrival found open 3 amp fuse, found short on the outside unit repaired short and test unit also installed new 3 amp fuse, check operation of ac unit found unit running on 14 split, check refrigerant pressures sub cooling was 5 with 30 super heat, added refrigerant now sub cooling is 11 and super heat is 15 supply/return air is now 18 would recommend upgrading unit due to refrigerant protocol office will emailed proposal for system replacement