Have any feedback for us? We'd love to hear it! Call us at (610) 595-9072 and let us know how we are doing.
Found inlet Gas Pressure of 2 stage 120K BTU propane furnace to be 3.00 In. W.C. Checked tank capacity. Gauge reads 75%. Cleaned flame sensor. Filter ok. Electric motors and components ok. Temp rise is low. Combustion test proves that system is running low on propane pressure. (3.96% CO2) Regulator has failed. Called Mrs. Saladino’s propane service provider with Mrs. Saladino. As of yesterday they no longer service regulators as a company. Recorded info of regulator to provide estimate for replacement. Urgent. Provide quote for replacement of regulator. Furnace will operate safely but with severely reduced efficiency until regulator is replaced.