Checked no heat complaint, found furnace short cycle the inducer again. Checked venting and condensate drains. Called tech support Brian McGraw, he asked to check ground, ok, he had me check the door switch, the incoming voltage 121.2 volts, check low voltage, 27.2 volts at common and W1. Never drops down or out. Brian wants us to replace the control board and harness. Called HVAC distributors and ordered parts. The have a board and they are looking for the harness.