No error codes at furnace. Checked temp rise. Checked static pressure. Checked flame sense. Observed thermostat complete the call fo heating. Checked for 24V at gas valve during appropriate point trial for ignition. Checked condition of burner. Tested condensate pump; noticed slightly weak performance. Found kink on vinyl that was partially limiting flow. Cut zip tie and freed kink. Retested condensate pump twice: ok. Although it did not occur during my time on the call the case could very well be that the pump safety was opening causing loss of voltage to stat. System is operating well at the time of this service.