Kurt M.

Kurt M.


Job Checkin

Found after giving thermostat a call for cooling fan came on and also compressor. Checked temperature split at package unit. Had about a 33 degree split and also heard a banging noise at the ceiling when blower first came on. Temperature on the supply side was around 36 degrees very close to freezing. Took off supply flex and found fire damper fusible link broken. Secured fire damper back open and zip tied flex back on. Will need to find a new fuseable link and return to install on fire damper. Will locate a reach out with a price to replace fusable link. For now System is cooling just fine with a 19 degree split. A/c is working fine at time of service.