Install a new Defrost Control Board for the Common Area/Hallway System. Control Board was previously removed from this Unit to get the system for Apartment 2106 running. Test operation of system upon completion. Installed new defrost board for hallway heat pump. Air handler is located in 2nd floor mechanical room. Cycled on heat pump at thermostat. Had a 19 degree temperature rise at air handler. Pressures were 343/94 at heat pump at 39 degrees outside temp. Heat pump is working fine again.