Checked no heat complaint, found furnace locked out on pressure switch, inducer runs but bearings are noises. Also pressures switch is not closing, switch is seeing.60†but has no pressure it closes at. Jumped out switch to test furnace, found blower whining and running at .88 amps rated at 9.2 amps. Blower motor is failing. Recommend replacing system due to amount of repairs required Need to set up sales call. With Mrs. Moore