No A/C found indoor blower running but no outdoor, check operation of compressor and fan motor, fan motor is open in overload, also capacitor reading zero both ends hermetic and fan side, quoted for repsirs called Jay and he approved repairs, after cooling down fan motor and replacing capacitor check operation of air conditioning system r22 pressures 220/75 with 30 super heat and 8 sub cooling manufacture calls for 10 sub cooling indoor txv indoor temp 80 outdoor 90 F supply air 62 return air 79 F 17 degree split