Evaporator coil replacement for Unit 3305 air handler. Made all necessary piping connection. Pressure tested to 300 PSI. Evacuated system to 480 microns. Charged system factory charge plus 13oz. (110 oz) R410A. Final temp split 19F. Subcooling 11.5; Superheat 9.5. 343HI pressure/146L0Pressure. Outdoor ambient 88.5F System is operating well at the time of this service.