Disconnect power to unit and remove existing Compressor from unit. Install new OEM Scroll Compressor and braze connections with nitrogen. Pressure test system with Nitrogen and leak test compressor fittings. Evacuate system to below 500 Microns and weigh in manufacturer's charge. Put system in cooling mode and measure refrigerant pressures. Add additional refrigerant to system charging by Subcooling/Superheat. 6/21/21: Compressor replacement for 2 Ton Ruud AC system Unit 6201. Removed existing compressor. Brazed new compressor while purging with nitrogen. Pressure test 365PSI passed. Evacuated system to 480 Microns. Using AtWater's refrigerant charged system. Factory charge 89oz. Added additional refrigerant until system was ooerating designed subcooling/refrigerant values. 363HI/140LO. 11.5 SC 18SH. 21F temp split. System is operating well at the time of this service.