No cooling. Keewon and Troy have been resetting breakers every 3 weeks as it has been randomly shutting off to allow this system to operate. Checked for 24V between Common and Y at outdoor. O Volts. Checked outdoor 40/5 Capacitor ok. Checked for open low and hi pressure cut off switches at outdoor control board. There are no open switches. Blower motor was running at fan only speed. Visual inspection of indoor control board shows extreme corrosion of board itself. Reset breakers cycled heat and cooling at thermostat. System ran well. Contacted Troy who approved replacing board with board from hallway system. Board on second floor hallway AirHandler was also fried and line voltage leads were disconnected. We took board from 3rd floor hallway air handler. During final conversation with Troy I explained that both the second floor hallway system and the third floor system hallway system are without indoor control boards. Troy will buy and install control boards for these air handlers