Luis T.

Luis T.


Job Checkin

Performed steam boiler cleaning tune up, flushed water and test low water cutoff and automatic feed, ok inspect sight glass, sight glass should get replaced for proper water level, cleaned burners check gas pressure ok, performed combustion test ok cleaned pig tail, check radiator that was not getting hot, noticed steam vent was not tight, tightened vent and check operation now radiator is getting hot.