Have any feedback for us? We'd love to hear it! Call us at (610) 595-9072 and let us know how we are doing.
Checked no cooling complaint in school store, found outdoor fan running but no compressor. Checked dual run capacitor ok. Checked start assist ok. Checked all wiring connections ok. Ohm compressor, found open windings. Recommend replacing system due to age and r22 refrigerant. Did not email