Installed new mini split system for the 3rd floor . We had to cut in a access hole in the knee wall to run the line set . We ran the line set through a knee wall to the roof eve . The line set then goes from the roof eve outside though slimduct to the mechanical rooms roof . We then went through the mechanical rooms roof into the mechanical room then came out of the mechanical room at ground level to the outdoor unit . We sealed up the holes with white caulk . We sealed the roof with roof tar . We made all low and high voltage connections . We flared the line set to the indoor unit and outdoor unit . We pressure tested , bubble tested , evacuated and charged the system to standards . We made the connection to the indoor condensate hose and ran it with the line set to ground level . We tested the condensate by pouring one gallon of water in the coil pan and watched it drain . We installed a new 15 amp double pole breaker in the electrical panel . We ran a new wire from the panel to the