520 Trestle Place
Downingtown, PA 19335
(610) 873-1244

Job Locations
for morgantown, pa


Map of Morgantown PA
Chris B.

Chris B.


Job Checkin

Upon arrival found Carlin combination primary/transformer locked out, check T T STATUS closed, check 115 volts to combination pri/trans ok getting 115 to tried to reset but was not able to reset,,,finally was able to reset, check cad cell reading 600 ohms, put in new cell temporarily for testing purposes reading 160. Primary went on locked out during testing, and couldn't reset it, would hold reset button for over 1 minute but still not resetting recommended replacing primary control ,,,,