Service call that the AC was not working and the Indoor Coil was frozen. System was turned off over night to thaw coil. Inspected accessible coil to ensure it was thawed. Tested system and found refrigerant charge low. Added 2 lbs of 410-A Refrigerant to system. Inspected Components on unit and tested Capacitor. Measured Voltage and Amp Draw on system. Cleaned EZ Trap and checked drain line to ensure it was clear. System operating to standards at this time. If system is loosing refrigerant than this indicates there is a leak present. The extent of the leak is not known at this time.