found 410a 3ton trane a/c system working fine when I arrived. Pressures were 378/142 at 93 degrees. Checked amp drawl on compressor, running load amp draw was 7.5 amps. Checked compressor start up amp draw was 23 amps, everything well in range. Homeowner talked about on Saturday when compressor first kicked on had a high draw on the panel and some circuits tripped. Talked to homeowner about adding a hard start kit for the a/c to help reduce the draw on the circuit. Added an spp6 hard start kit an re checked the start up amp draw was 16 amps. System is working fine at time of inspection.