Found system not running. Talked to homeowner about situation and found out that every once and a while over the past few days the system would come on for a little while then shut down again. Found water on the floor around package unit. Pulled off doors and found condensation drain backed up which caused ez trap to pop up and turn off system. Water level must have went down at times and a/c would run for a while till drain backed up again. Blew out condensate drain and tested drain with about 1 gallon of water. Condensation drain is now draining. All condensation lines are tied into a larger line which runs down to the ground level.