Ran ne 3/4 x3/8†lineset down slimduct and through basement to reconnect outdoor unit to indoor air handler. Used press and sweat fittings. Brazed with nitrogen and did a pressure test a 300 psi and bubble checked. Vaccumed down to 330 microns and released refrigerant charge. Checked 410a pressures at 88 degrees. Pressures were 352/102 with 15 subcooling. Checked temperature split had a 17 degree temperature split. System is working fine at time of service.