Performed heat pump check up check, upon arrival found unit not working thermostat calling for heat but unit not running, found no 24 volts on terminals, open fuse, check all wiring ok, replace fuse and test unit check indoor and outdoor wiring ok no issues found, check electric heat back up ok new filter, check outdoor unit 410 pressures ok capacitor and contactor ok test defrost ok no Shorts were found all components and wiring checked out ok amp draw on red hot side of low voltage transformer is .4 amps on y goin to outdoor heat pump .2 amps