Geothermal system not working, will work for about 20 mins then would shutdown, check operation check water temp in and out ok 9 degree difference also check supply and rerun air supply 49 return 69 check refrigerant charge ok, unit goes into loss of charge code, bypassed switch for testing and unit works fine no codes and continues to run, faulty switch, we will need to contact manufacturer see if we can add loss of charge on suction line of refrigerant line if not major work will be involved, we will get back to customer once we find out from manufacturer also informed customer about evap coil being dirty