Kurt M.

Kurt M.


Job Checkin

After talking to homeowner about issue, he had mentioned that about 2 nights ago he had noticed the outdoor heat pump running, but not the fan at the indoor blower. Put gauges on system and got homeowner to give a call for heating. Called tech support and gave them model and serial numbers of indoor and outdoor heat pump. Had pressures ind heating mode at 68 degrees of 326/123. He wanted me to check the super heat in heating mode and verify static pressure. Static pressure was .5 w.c. . And had a super heat after 15 minutes of run time of 9.8. He had mentioned that possibly the ice cube relay inside the air handler was not picking up the fan, but homeowner said he had no issues in cooling mode. Told Phillip to keep any eye on it and give us feed back if he notices outdoor unit running with out the indoor blower,