Replaced blower motor, blower relay, motor wiring harness , and t-4 thermostat. Cycled on heat pump system in heating mode. Outdoor ambient air temperature is 46 degrees. 410a refrigerant pressures in heating mode are 291/103. Checked temperature rise in heating mode and it was exactly 20 degrees. Had Eric from hvac check over everything. We jumped out the indoor fan motor at wiring strip from rot g terminals and r to w terminals. Heat pump is cycling on and of correctly at time of service.