No heat, found unit off, wires W and R were disconnected at the control, check furnace operation and found broken inducer blower motor wheel, also found weak blower assist 75 mf reading 56 informed customer and quoted for repairs. I will check availability tomorrow mourning, we will get back to customer on what’s the time frame, 02/11/20 installed new inducer assembly and also new run blower capacitor, check furnace operation, run heater for 20 mins and performed combustion test, co looks ok, exhaust temps is little higher, check temp split on furnace supply 130 return 75, informed customer about situation, heat exchanger is not rejecting all the heat completely, internal parts wearing out, blower wheels is little dirty, cleaning blower wheel would help heat transfer better off exchanger