No ac, found Susie, off upon arrival informed customer to set thermostat cool 65 and indoor blower runs but no outdoor, found open hermatic side on cap, quoted for new cap, once new cap is installed I will amp draw and voltage, check refrigerant pressures, customer ok repair cost, installed same rating cap and check ac operation check amps going to motor and compressor, ok amp draw motor is just below the maximum rating, check refrigerant charge 410 ok 300/145 supply air 53 return air 77