Performed QA on Amana Heat Pump system. Completed checklist form in system. Tested system in Heating and Cooling modes. Had System in cooling mode and was inspecting the Low voltage wiring at the outdoor unit. When moving the wiring, the fuse on the AHU blew. Found a small Knick in one of the low voltage wires. I could have caused this when I was pulling the wires out and moving them. Taped the low voltage wires at the outdoor unit and replaced the indoor fuse. Retested system and found no further issues. Tested system in Heating Mode and Cooling Mode. Tested Condensation Pump and tested EZ Trap Float Safety. When we return for a six month inspection will need to add a trap to the vinyl tubing. Will need to either replace all of tubing or add some 3/8†Copper pipe and extend the tubing so we can add a trap to it before it goes into the sewer pipe. Total length of tubing is 15-20’.