Found blank Honeywell thermostat. Checked for 24V between R and C at indoor control. Ok. Found no common conductor at tstat and the terminal screw for common terminal is missing. Replaced AA batteries. Thermostat display was energized. Set date and time. Made call for cooling. Cleaned trap. Tested pump. Checked temperature split. Provided estimates to replace Tstat. System is operating well at the time of this service.