Arrived and checked smoke when system was running, had a 9 on the scale, checked nozzle and z dimension, found that the previous tech had installed a .85/80°B nozzle, data plate calls for a .65/80°A. Changed nozzle, adjusted primary and secondary air. Checked smoke and combustion and everything is working correctly at this time with 0 smoke and 10.9%CO2.