Service call that the Heat was not working. Turned system on and found Inducer Motor was running but the pressure switch was not closing. Found the Intake Exhaust Pipe was blocked. Cut 3” Exhaust Pipe due to being glued into the Furnace. Cleaned Intake and reassembled. Put system in operation and performed Combustion Analysis on Furnace. Cycled system multiple times to insure it was firing and running properly. Also found the Orifice on the Pressure Switch had been removed. Reinstalled the Orifice and put back in operation. Inspected the Vent Pipes on the exterior of the home. The Exhaust Vent Pipe is pitched incorrectly in the basement above the unit. This could cause excess water to accumulate and not drain due to being pitched away from the unit. While system is currently operating this could cause intermittent problems. Included estimate for the repair of the exhaust Pipe so it is pitched properly.