No air conditioning, found system off upon arrival set thermostat to call for cool and check operation supply air 55 return air 66 check blower motor and cap air filter ok, check outdoor unit refrigerant pressures found to be high sub cooling and high super heat, pressures did not match corresponding PT CHART on manufacture specifications, removed bulb from suction new txv is needed