Inspected ductwork in attic space and found one run kinked feeding Father Michaels bedroom. Recommend installing top take off and panning off other supply. Checked all dampers and found only chapel and supply runs where bedroom is located dampened down. Measured airflows to each space. During visit encountered a problem with thermostat no reading correct temperature. Thermostat reading 68 and setpoint at 71 and thermostat not starting. Removed from wall and placed back on wall and temperatures went to 74/74 and unit came on. Replaced thermostat with Honeywell T6 wifi and setup and tested operation. Left fan in On position.