Have any feedback for us? We'd love to hear it! Call us at (610) 595-9072 and let us know how we are doing.
Water leak, found existing drain line came apart,connections was glued but it is old, recommend replacing trap and some fittings customer ok with repairs, replaced 3/4 pvc trap and coupling/below, check drain ok check ac operation ok 410 pressures ok 290/140 9 super heat 7 sub cooling check temp split supply air 59 return air 76