Performed two ac tune ups, check electrical low and high replace filter 16x25x1 and 16x20x1 flushed drains ok check split ok, outdoor units r22 ok first floor contactor and cap ok, on second floor unit found weak capacitor 35/5 reading 27/4.5 also fan motor is running at .65 amps rated at .5 amps, informed customer about situation and recommend repairs would recommend getting estimate to replace ac unit due to age Office to follow up with customer