Installed amana ac system. Flushed and adapted to 7/8 3/8 lineset. Leak checked and vacuumed down system to 380 microns. Tested condensate drain and pump with water. Checked delta t at air handler it was 19 degrees. Checked refrigerant pressures and temperatures at outdoor unit. System is working at manufacture specifications.