Job Checkin

Found bad blower motor. Found furnace running and control board sending 120v to blower motor. Homeowner replaced capacitor earlier today which capacitor tested ok. Found motor has failed. Replaced blower motor with motor 1/2h.p. Motor had on truck and performed combustion test. Furnace is back up and working fine again. Offered membership, homeowner just wanted to repair at this time.