Performed cooling maintenance on attic second floor heat pump. Cleaned condensate trap and drain. Replaced air filter. Checked voltage, amperage and electrical connections. Measured capacitor values ok. Started heat pump, checked refrigerant charge, found system low on charge. Topped off refrigerant charge, balanced charge by sub cooling. Checked operation and temperature drop across coil. Need to schedule first floor cooling maintenance. Need to quote to level first floor outdoor unit