Service Call Fee: Cleaned the flame sensor and verified operation. Looks good. Checked the gas pressure and performed a combustion analysis. These looked good. Furnace went out on high temperature limit. The return is being blocked with a coil from a wood burning stove that was installed into the ductwork. System wasn’t designed for this add on. System is functioning properly.