Service Call Platinum Client- no current codes when I arrived. no issues found with heat pump. Suction pressure 110, liquid pressure 320. According to charging chart these pressure are correct(113/323). Heat rise of 19 with heat pump. Voltage issue has been fixed from last visit after power company replaced some old equipment. System is running well.