Arrived to find unit tripped out on high limit. No fan operation, motor bad on furnace, as well as capacitor motor drawing 12.7 amps and cap tested out 1.3 uf. Goodman furnace (1999) upon inspection it was discovered that vent flue to inducer motor was completely detached from transition collar.