Kyle P.

Kyle P.


Job Checkin

Service Call Platinum Client upon further diagnosis did clean flame rod and do believe unit to be overlimiting did disconnect byass on humidifier (it was piping supply air right back into return causing abnormal temp rise. did check drainage did nit find any issues. units temp rise was approximately 58 degrees co(0) was approximately 67 ppm did not get unit to have a malfunction problems could have been possibly flame rectification and or limit issues did address both issues. however unit is from 2003 and is in very poor condition do recommend replacing unit did set up quote for 1/5/22 also did check venting did not see any issues.

Service Call Platinum Client

upon further diagnosis did clean flame rod and do believe unit to be overlimiting did disconnect byass on humidifier (it was piping supply air right back into return causing abnormal temp rise. did check drainage did nit find any issues. 

units temp rise was approximately 58 degrees 

co(0) was approximately 67 ppm 

did not get unit to have a malfunction problems could have been possibly flame rectification and or limit issues did address both issues. however unit is from 2003 and is in very poor condition do recommend replacing unit did set up quote for 1/5/22 
also did check venting did not see any issues.