Performed Platinum Comfort Club Membership Tune-Up on Heating System did preform, heating check did clean flame sensor spade was corroded did clean connection gas pressures were 3.11 temp rise approximately 51 did replace blower capacitor tested 12.99 (15mfd) blower pulling approximately 7 amps inducer approximately 0.56 did add surge protection to furnace did verify reme was working all combustion analysis met safety and manufacturing parameters. did soap drains and collector box