Service Call After Hours Fee- heat pump fault code flashing 3 times for high pressure lockout. Reset power to board and got system running. Outside temperature is 88 degrees, low side pressure is 150, high side 320. Sub cooling of 14. Condenser coil looks clean on the heat pump. Customer said they changed filters this morning and they were very dirty. Inside air handler looks good.

Service Call After Hours Fee- heat pump fault code flashing 3 times for high pressure lockout. Reset power to board and got system running. Outside temperature is 88 degrees, low side pressure is 150, high side 320. Sub cooling of 14. Condenser coil looks clean on the heat pump. Customer said they changed filters this morning and they were very dirty. Inside air handler looks good.