Bradley M.

Bradley M. Job Checkin

Checked and cleaned all components. Tightened wiring connections. Hot surface igniter is testing out of range at 93 ohms. Control board has been replaced previously. Blower capacitor is testing below spec at 3.8/5uf. Capacitor is leaking fluid. Blower motor is leaking oil. Blower wheel has some build up on it. Duct system is in very poor condition. Emergency drain pan is rusted. System is currently operational, but in overall poor condition. Recommend replacing hvac equipment and ductwork due to age, operating condition/cost of repairs, efficiency and reliability.