Chemically cleaned and pressure washed condenser coil. Coil is pretty damaged and i would not recommend another pressure wash to avoid and further damage to coil. If head pressure is an on going issue condenser coil may need to be replaced. Checked pressure after coil dried and they were found normal around 70/205. Vacuumed all water from unit and floor in mechanical room. Found hot water coils valves still open and water still in coil. Closed off hot water valves and drained coil for summer season. Left unit on cooling and operating normally at this time.