Order parts Monday and return. Returned and installed new defrost control board with defrost sensor. Since this is second time part has failed I tested unit thoroughly. Found that after unit ran awhile condenser would intermittently kick out. Found bad connection to common wire at air handler. Connected would intermittently connect then rattle and loose connection. Repaired connection. Cycled unit in all modes. System is on north side of house and maybe getting a little more abuse than normal. As a precaution installed a small piece of guttering over unit. Install thermostat to shut unit off at freezing temperature and also gave further education on emergency heat setting. System is heating at this time. System was frozen solid outside apon arrival. Unthawed unit and washed slightly dirty coil so unit could be tested. Cycled unit multiple times in all modes. Unit under warranty no charges to customer.