9320 S. Pole Rd
Oklahoma City, OK 73160
(405) 794-8900

Our Top Cities


Job Locations
for edmond, ok


Map of Edmond OK
Ray F.

Ray F.


Job Checkin

Ray F 8/4/22 Arrived to a silver club member ac tune up and the customer’s father met me at the residence. I inspected the condenser and found the refrigerant charge to be normal. Contactor, wiring and disconnect n good condition. Capacitor is within manufacturer specifications. Compressor and condenser fan motor amps are ok. Inspected evaporator coil and found it to be clean. The blower motor, wheel and housing are clean. Blower motor amps are normal. Return and supply temperature differential of 21 degrees. Condensate drain line is clear. Cleaned condenser coils. System is working properly at this time. Thank you for your business.