08JUN2024 Jason Brown Arrived for new customer no cool. Spoke with homeowners about the systems performance. It went out yesterday we tried replacing the fuse, but it just popped again. Inspected equipment found contactor coil shorted to ground. With homeowner permission I replaced the contactor and fuse then cycled the equipment. Checked amps, pressures and all components. System is cooling properly at this time 20 degree delta temperature. While out we discussed maintenance contracts and priority service. Homeowner will call in next week to sign up.