I came out for a no cool. I checked the system over and found the condenser fan not running. The bull capacitor is reading 0 on the fan side. The condenser fan spins freely, so the bearing aren’t locked up. Got approval from home warranty company to replace the bad dual capacitor. I installed a new capacitor, washed the condenser coil off and cycled the system. I checked all operations. Condenser fan running at 1.1a. Max = 1.7a. all working properly.