9320 S. Pole Rd
Oklahoma City, OK 73160
(405) 794-8900

Our Top Cities


Job Locations
for moore, ok


Map of Moore OK
ADAM  R.

ADAM R.


Job Checkin

I came out for a not cooling well. I checked the system over and cycled the ac. The head pressure was 40 degrees over ambient and the SH was high. With approval. I washed the condenser coil, which was plugged with dirt. I cycled the system again and the head pressure dropped 20 degrees. I added 1lb of r22 and set the SH to 22 and it was calling for 24. The system is getting older. I’d recommend saving for a new one. All working at this time.