Blue shield summer service. Replaced filter, blower motor is an ECM motor, run capacitor is not required, motor and wheel are clean, indoor coil is clean, condensate drain line is clear. Washed condenser coil, compressor side of dual run capacitor tested bad, rated at 45uf, actual was 11.8uf, homeowner wants to wait to replace capacitor. Contactor points are good. Checked operation, all amps and pressures are good. Required subcooling is 8 degrees, actual subcooling was 7.7 degrees. System is operating normally